Factory-direct · CCCF & ISO certified Sales: [email protected]
🔥 KitchenFireGuardby Zhongzhi Tianlong Get a Quote

Single-tank system · 9 L agent

CMJS9-1 Kitchen Fire Suppression System

Compact single-tank wet-chemical system for smaller cook lines. Protects up to 9 hazard units — one 600 mm fryer/wok per unit, or one 400 × 400 mm duct port per unit.

  • 🔥 183°C fusible-link activation — no power needed
  • ⏱️ Flame knock-down in 3–5 seconds
  • 🚫 Automatic gas shut-off + sounder alarm
  • 💧 Water cool-down cycle after discharge
  • 📱 Optional smart-cloud alerts to phone/PC

Request CMJS9-1 Pricing

USD 1,800 FOB per system, standard configuration · what that price includes

CMJS9-1 system with agent tank and nitrogen cartridge CMJS9-1 cabinet front panel with operating instructions

Technical Specifications

ModelCMJS9-1 (single tank group)
Extinguishing agentPotassium-acetate based wet chemical, 9 L
PropellantNitrogen cartridge (mechanical actuation)
Protection capacity9 hazard units — one Φ600 mm fryer/wok or one 400×400 mm duct port per unit
ActivationFusible link, 183°C (manual / emergency pull as backup)
Extinguishing time3–5 seconds from discharge
Post-discharge coolingWater valve opens automatically ~10 s after agent discharge
Fuel safetyAutomatic gas-valve shut-off, audible-visual alarm, optional BMS/central-station link
Cabinet dimensions470 × 600 × 200 mm (W×H×D), wall-mounted
Power requirementNone (detection & discharge fully mechanical)
Smart monitoringOptional cloud module — alerts to mobile app / PC terminal
Design standardsGA 498-2012 · GB 50016-2014 · CECS 233:2007
CertificationCCCF fire-product certified (valid to Jun 2029); type-tested by the National Fixed Fire Extinguishing Systems QA & Test Centre
CMJS9-1 system layout diagram
Typical installation — the cabinet connects to detection lines over the range and in the exhaust duct, plus gas shut-off and water cool-down.
Operating & care notes — 9 rules for daily use of the CMJS system (1’47”).

Sizing guide

Each hazard unit covers one standard 600 mm fryer or wok station, or one 400 × 400 mm exhaust-duct opening. Count your appliances and duct ports, add 20% spare capacity for future line changes — if the total is 9 units or fewer, one CMJS9-1 is enough. Above that, step up to the CMJS18-2 dual-tank system.

🛢️

1 fryer / wok ≤ Φ600 mm

= 1 hazard unit

🌬️

1 duct port 400 × 400 mm

= 1 hazard unit

📦

Not sure? Send the layout

We size it for you free of charge

What happens in the first 60 seconds

A cooking-oil fire doubles in size faster than a manual response can follow. The CMJS9-1 does not run its actions one after another — detection, discharge, gas shut-off, alarm and cool-down overlap, and the whole sequence is over in about a minute. The flame itself is out in 3–5 seconds.

🌡

1 · Detect at 183°C

A fusible link sits above every protected appliance and duct opening. At 183°C the link separates and releases the mechanical actuator. Normal cooking temperatures never reach it, so steam, smoke and spatter do not trip the system.

💣

2 · Discharge in 3–5 s

The nitrogen cartridge ruptures the tank diaphragm and pressurises the 9 L of wet chemical. It leaves the nozzles as a fine mist at a steady pressure, so hot oil is not splashed out of the pan.

🔒

3 · Cut the gas

The same mechanical stroke closes the gas shut-off valve on the incoming line. Removing the fuel is what stops a wok fire from re-igniting after the agent has knocked it down.

🚨

4 · Alarm and notify

A local sounder and beacon run in the kitchen while a dry contact reports the discharge to the building management system or fire control room. Staff know instantly which kitchen has a problem.

💧

5 · Cool with water

About 10 seconds after the agent finishes, the water valve opens and sprays the range and duct. Cooling the oil below its ignition point is what prevents the classic re-flash two minutes later.

✋

Backup · Manual pull

Every installation includes a manual pull station at the kitchen exit, plus an emergency button on the cabinet. Both use the same discharge path as automatic activation.

What ships in the cabinet

The CMJS9-1 is supplied as a complete, pre-assembled system — not a tank that still needs half the components sourced locally. Nozzles are selected against your appliance list before shipment, so the pipe kit arrives matched to your cook line.

Agent tank9 L potassium-acetate wet chemical, formulated for cooking-oil (Class F) fires. Non-toxic, odourless, and cleaned up with plain water.
PropellantSealed nitrogen cartridge. Stored pressure is released only at activation, so the tank is not under load while it waits on the wall.
Detection183°C fusible links on stainless-steel cable, one above each hazard unit and one at each duct opening.
DischargeAtomising nozzles sized to burner diameter and duct-port area, plus a dedicated duct nozzle. Stainless steel, copper and alloy-aluminium pipework with anti-corrosion treatment.
ActuationMechanical control valve, manual pull station, emergency button on the cabinet front.
InterlocksGas shut-off valve link, water cool-down valve, sounder and beacon, dry contact for BMS or fire panel.
Monitoring (optional)Cloud module reporting discharge, valve status and service dates to a phone app or PC terminal.

Site requirements before you order

Four things on site decide whether a CMJS9-1 installs cleanly. Send photos of each with your inquiry and we will confirm the layout before the cabinet is built — this is the step that prevents most on-site surprises.

Wall spaceA clear wall area for the 470 × 600 × 200 mm cabinet, outside the direct splash zone of the range and within reach of the manual pull handle. The cabinet is wall-mounted and takes no floor space.
Gas lineAn accessible shut-off valve on the incoming gas line that the system can close on activation. If the kitchen runs on LPG cylinders, tell us the arrangement.
Water lineA cold-water supply for the post-discharge cool-down cycle, with a valve the system can open.
Duct accessEach 400 × 400 mm duct opening needs a nozzle position and a service access point. Grease-filled ductwork without access cannot be protected properly.

Retrofit is normal for this system: the work happens during a scheduled kitchen shutdown, and the range does not have to be removed. Typical installations are completed in a single day per cook line. Send your kitchen layout and we will return a nozzle plan and a bill of materials.

Which standard applies to your project

Kitchen suppression is one of the few product categories where the local standard decides what you are allowed to install. Being clear about this at inquiry stage saves months — so here is exactly where the CMJS9-1 stands.

China — GA 498-2012The design, installation and acceptance standard for commercial kitchen cooking-area suppression. The CMJS9-1 is CCCF certified and type-tested by the National Fixed Fire Extinguishing Systems Quality Supervision and Testing Centre against this standard.
United States — NFPA 17A / UL 300NFPA 17A governs wet-chemical systems and UL 300 is the fire test that listing is based on. This model is not UL listed. If your project is specified to UL 300, tell us before design freeze and we will confirm what documentation we can supply.
Europe — EN 16282 / local codesEuropean projects generally require a CE-marked system under the applicable harmonised standard. The CMJS9-1 does not carry CE marking for this model; treat it as a China-standard system unless your consultant accepts CCCF documentation.
Middle East, Africa, Southeast Asia, Latin AmericaMany projects in these markets accept a CCCF-certified system with a full type-test report, or specify performance requirements rather than a named listing. This is where the CMJS9-1 is most often supplied.

Full certificates, type-test reports and the manufacturer’s ISO 9001 / 14001 / 45001 documents are on the certifications page. We send the complete pack as PDF with every quotation, so your consultant or fire authority can review it before you commit. Unsure how CCCF compares with NFPA 17A or UL 300? The standards guide explains what each document governs.

CMJS9-1 or CMJS18-2?

Hazard units protectedCMJS9-1: up to 9  |  CMJS18-2: up to 18
Agent volume9 L single tank  |  18 L (2 × 9 L) dual tank
Cabinet footprint470 × 600 × 200 mm  |  690 × 600 × 200 mm
Typical kitchenSingle outlet, café, small QSR, staff canteen  |  Hotel banquet kitchen, chain restaurant, central kitchen
Choose it whenYour count is 9 units or fewer with no planned expansion  |  You are at 10–18 units, or at 7–9 with a planned line extension

Not sure which way the count falls? Read how a kitchen fire suppression system works first, then send us your appliance list — sizing is free and takes one working day.

Buyer questions on the CMJS9-1

How many fryers or woks can one CMJS9-1 protect?
Nine hazard units. One wok or fryer up to 600 mm diameter counts as one unit, and one 400 × 400 mm exhaust-duct opening counts as one. Count your appliances, add about 20% for future line changes, and if the total stays at nine or below a single CMJS9-1 covers the kitchen.
Does it need mains power to work?
No. Detection is a fusible link and discharge is driven by a nitrogen cartridge, so the system protects the kitchen during a power cut — which is exactly when a kitchen is most likely to have an unattended pan. Power is only needed for the optional cloud monitoring module.
Will steam or smoke set it off?
No. The trigger is temperature at the link, not smoke or airborne grease. The 183°C threshold sits well above normal cooking and hood temperatures, which is why mechanical links are used instead of electronic heat detectors in this position.
Can it be retrofitted into an operating kitchen?
Yes, and that is the majority of our installations. The cabinet is wall-mounted, the pipework follows the hood and duct, and the work is scheduled during a shutdown window. A single cook line is typically completed in one day, including commissioning and the acceptance test.
What has to be replaced after a discharge?
The agent tank is refilled, the nitrogen cartridge and every fusible link are replaced, and the nozzles are cleaned and checked. We supply a spare-link kit with every system so the kitchen is not waiting on a shipment after a real event.
How is it maintained?
Scheduled inspection at the interval your local authority requires — typically every six months for a commercial kitchen. The check covers link condition, nozzle blockage, tank pressure, valve operation and the gas shut-off linkage. A maintenance checklist ships with the unit, and the optional cloud module flags upcoming service dates automatically.
What do you need from me to quote?
An appliance list or kitchen plan (burner count, wok diameters, fryer sizes), the number of duct openings, the destination port and the quantity. With those four items we return a sized system, a bill of materials and a quotation within one working day. Current price drivers are broken down in the cost guide.

Need the dual-tank version?

CMJS18-2 doubles the agent and protects up to 18 hazard units — built for full hotel and chain-restaurant cook lines.

View CMJS18-2